RIDDER'S
Terlicht
45
9451
Kerksken
Belgium
phone:
00-32-53-833512
fax:
00-32-53-840994
e-mail
ridders.pack@pandora.be

The right support and after
sales service. This is what we give you day after day and this 24/24
and 7/7

|
You can ask your questions direct by using ICQ when
we are online. Our ICQ number is 163202313.
If
you do not have ICQ, please download it for free at www.icq.com


I-7000 Analog I/O
Expansion
You can greatly expand the analog
I/O capability of any T100MD or T100MX PLC using these I-7000 modules connected
to the M-series RS485 port. Up to 31 units of I-7000 may be multi-dropped on the
RS485 bus.

Application Notes
& Sample Programs: Download
zipfile
The expansion module are all
optically isolated from the PLC. We offer the following models for direct sales
to our PLC customers:
|
I-7017: 8 Channel, 16-bit Analog Input
Module
|
I-7018: 8 Channel 16-bit Thermocouple
Input
|
|
T100MD Super PLC & Options
Analog Input
-
Channels: 8 differential or 6 differential
and 2 single- ended by jumper select
-
Resolution: 16-bit
-
Input type: mV, V , mA (with external 125 ohms
resistor)
-
Input range: ± 150mV, ± 500mV , ± 1V, ± 5V, ±
10V and ± 20mA
-
Sample rate: 10 Samples/Second
-
Bandwidth: 15.7 Hz
-
Accuracy: ± 0.1%
-
Zero drift: ± 20uV/¢XC
-
Span drift: ± 25ppm/¢XC
-
CMR @ 50/60 Hz: 86 dB min
-
NMR @
50/60 Hz: 100 dB
-
Input Impedance: 20M Ohms
-
Over voltage protection: ± 35V
-
Isolation:
3000Vdc
Communication
Interface
RS-485
Power Supply
|
T100MD Super PLC & Options
Analog Input
-
Photo-isolation: 3750
Vrms
-
Type: mV, V , mA (with external 125 ohms
resistor)
-
Thermocouple: Type J, K, T,
E, R, S, B, N, C
-
Channels :
8 differential or 6 differential and 2 single-ended by jumper
select
-
Voltage range: ¡Ó15mV, ¡Ó 50mV , ¡Ó 100mV, ¡Ó 500mV, ¡Ó 1V, ¡Ó 2.5V
-
Current range: ¡Ó 20mA
-
Sampling rate: 10
Samples/Second
-
Bandwidth: 15.7 Hz
-
Accuracy: ¡Ó 0.1%
-
Zero drift: ¡Ó 25uV/¢XC
-
CMR @ 50/60 Hz: 150 dB
-
NMR @ 50/60 Hz: 100 dB
-
Span drift: 25ppm/¢XC
-
Over voltage protection: ¡Ó
35V
-
Isolation:
3000Vdc
Communication
Interface
RS-485
Power Supply
-
Input : 10~30Vdc
-
Consumption: 1.0W
|
|
I-7022: 2 Isolated Channel,
12-bit Analog Output
|
I-7024: 4 Channel, 14-bit
Analog Output
|
|
T100MD Super PLC & Options
Analog Output
-
Photo-isolation: 3750 V
rms
-
Channels: 2
-
Channel to channel isolation
-
Output type: mA, V
-
Output range:
0 to 20mA , 4 to 20mA and 0 to 10V
-
12-bit resolution
-
Accuracy: ¡Ó 0.1% of FSR
-
Read back accuracy: ¡Ó 1% of FSR
-
Resolution: ± 0.02% of
FSR
-
Zero drift:
Voltage output: ¡Ó 30uV/¢XC
Current output: ¡Ó 0.2uA/¢XC
-
Span temperature coefficient: ¡Ó 25ppm/¢XC
-
Programmable output slope:
0.125 to 1024 mA/second
0.0625 to 512 V/second
-
Current load resistor:
Internal power: 500 ohms
External 24V: 1050 ohms
Isolation: 3000Vdc
Communication
Interface
RS-485
Power Supply
-
Input: + 10 to 30Vdc
-
Consumption: 3.0W
|
T100MD Super PLC & Options
- Output range :
0 to 20mA , 4 to 20mA and 0 to
10V
- Programmable
output slope (16 types) :
0.125 to 2048mA/sec 0.0625 to 1024 V/sec
Analog Output
-
Photo-isolation: 3750
Vrms
-
Indication LED Light: for power and communication
-
Channels: 4
-
Output type: mA, V
-
accuracy: ± 0.1% of FSR
-
Resolution: ± 0.02% of FSR
-
Zero drift:
Voltage output: ¡Ó 30uV/deg C
Current output: ± 0.2uA/deg C
-
Span temperature coefficient: ± 20ppm/ C
-
Current load resistor: External +24V power: 1050
Ohms
Communication
Interface
RS-485
Power Supply
|
*All prices are without VAT and import taxes. Ask net prices
in Euro.
|