You can ask your questions direct by using ICQ when
we are online. Our ICQ number is 163202313.
If
you do not have ICQ, please download it for free at
www.icq.com
File and Email
Services
The new version 2.0 of TLServer provides a
number of File and Email services to the PLCs via the serial
comm port. Basically a PLC can send service requests to the TLServer using
"tags" (which are ASCII characters enclosed between the '<' and '>'
characters) and the TLServer will perform the service requests upon receiving
valid commands. The PLC can easily send the tags and ASCII data using the TBASIC
PRINT #n command.
Since the PLC is the one which initiates the
service request, it does not need to be linked to the TLServer all the time
unless it needs to request a service from the TLServer. This makes it possible
for a remote PLC to connect to the TLServer via the telephone line using a modem
and perform the required file or email services, then disconnects itself from
the TLServer so that other PLCs can take turns to connect to the TLServer to
request for services.
The following are the currently support file
and email services that the TLServer 2.0 provide for the super PLCs
|
1. Write data to
file (the existing file will be
overwritten) |
Format: <WRITE [filename]>
data data data... data.... </> |
|
2. Append data to
file (new data are added to the
existing file)
|
Format: <APPEND [filename]> data data
data... data.... </> |
|
3. Email data to
recipient
|
Format: <EMAIL [email address]> Sender: [sender
email] Subject: [subject text] data data data... data....
</> |
| 4. Read Data from
File
|
Format: <READ [filename]>
</> |
5. Read Real Time Clock
From TLServer |
Format: <READ
RTC[]></>
| |